DUTREAT SERIES (DT) SMALL:
Unit Model | DT – 500/2.5 | DT – 800/4 | DT – 800/6 | |||
---|---|---|---|---|---|---|
Air Flow Capacities | ||||||
Supply (Treated) Air | 850 M3/h | 500 CFM | 1,360 M3/h | 800 CFM | 1,360 M3/h | 800 CFM |
Regeneration Air | 765 M3/h | 450 CFM | 1,190 M3/h | 700 CFM | 1,190 M3/h | 700 CFM |
Refrigerant | R-407C | |||||
Desiccant Solution LiCl (40% Concentration) |
55 Liters | |||||
Operation Temperature Range | From (-) 10 °C to (+) 50 °C | |||||
Operation Abs. Humid. Range | From 1 g/Kg to 30 g/Kg | |||||
Electrical System | 380V, 3Ph, 50Hz | 460V, 3Ph, 60Hz | 380V, 3Ph, 50Hz | 460V, 3 Ph, 60Hz | 380V, 3Ph, 50Hz |
60Hz 460V, 3Ph, |
Line Current Amp. | 5-9 | 8-12 | 12-16 | |||
Breaker Size Amp. | 16 | 20 | 25 | |||
230V, 3 Ph, 60Hz | 230V, 3 Ph, 60Hz | 230V, 3 Ph, 60Hz | ||||
Line Current Amp. | 8-15 | 13-20 | 20-26 | |||
Breaker Size Amp. | 25 | 32 | 40 |
Compressor Size | 2.5 HP | 4.0 HP | 6.0 HP | |||
Sensible Cooling | 2.8 kW | 9,500 Btu/h | 3.1 kW | 10,600 Btu/h | 3.5 kW | 11,900 Btu/h |
Latent Cooling | 6.7 kW | 22,900 Btu/h | 9.9 kW | 33,800 Btu/h | 11.3 kW | 38,600 Btu/h |
Total Cooling | 9.5 kW | 32,400 Btu/h | 13.0 kW | 44,400 Btu/h | 14.8 kW | 50,500 Btu/h |
2.7 TR | 3.7 TR | 4.2 TR | ||||
Moisture Extraction | 9.5 Lit./h | 14.0 Lit./h | 16.8 Lit./h | |||
Temperature Reduction | 10 °C | 7 °C | 8 °C | |||
Efficiency Rating (3) | 2.7 COP | 9.2 EER | 2.5 COP | 8.5 EER | 2.1 COP | 6.4 EER |
Weights | Kg | Kg | Kg |
Net | 230 | 240 | 295 |
Operating (including LiCl) | 320 | 330 | 385 |
Dimensions | mm | mm | mm |
L | 1,140 | 1,140 | 1,580 |
W | 1,200 | 1,200 | 1,200 |
H | 1,100 | 1,100 | 1,100 |
Clearances | mm |
I | 1,000 |
II | 500 |
III | 100 |
TECHNICAL SPECIFICATIONS:
DuTreat (DT) Large
Unit Model | DT – 1400/5 | DT – 2400/7 | DT – 3400/9 | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Air Flow Capacities | ||||||||||||
Supply (Treated) Air | 2,380 M3/h | 1,400 CFM | 4,080 M3/h | 2,400 CFM | 5,780 M3/h | 3,400 CFM | ||||||
Regeneration Air | 2,380 M3/h | 1,400 CFM | 4,080 M3/h | 2,400 CFM | 5,780 M3/h | 3,400 CFM | ||||||
Refrigerant | R-22 or R-407C | |||||||||||
Desiccant Solution LiCl (40% Concentration) |
125 Liters | |||||||||||
Operation Temperature Range | From (-) 10°C to (+) 50°C | |||||||||||
Operation Abs. Humid. Range | From 1 g/Kg to 30 g/Kg | |||||||||||
Electrical System | 380V, 3 Ph, 50 Hz |
460V, 3 Ph, 60Hz |
208- 230V, 3 Ph, 60Hz |
380V, 3 Ph, 50 Hz |
460V, 3 Ph, 60Hz |
208- 230V, 3 Ph, 60Hz |
380V, 3 Ph, 50 Hz |
460V, 3 Ph, 60Hz |
208- 230V, 3 Ph, 60Hz |
|||
Line Current Amp. Breaker Size Amp. |
17.3 | 14.5 | 33.3 | 20.3 | 17 | 39.3 | 29.5 | 22.1 | 49.5 | |||
25 | 20 | 40 | 30 | 25 | 50 | 50 | 30 | 80 |
Compressor Size | 5 HP | 7 HP | 9 HP | ||||||
Sensible Cooling | 5.4 kW | 18,400 Btu/h | 9.3 kW | 31,700 Btu/h | 13.2 kW | 45,100 Btu/h | |||
Latent Cooling | 13.9 kW | 47,500 Btu/h | 23.8 kW | 81,300 Btu/h | 33.7 kW | 115,100 Btu/h | |||
Total Cooling | 19.3 kW | 65,900 Btu/h | 33.1 kW | 113,000 Btu/h | 46.9 kW | 160,200 Btu/h | |||
5.50 TR | 9.42 TR | 13.35 TR | |||||||
Moisture Extraction | 19.6 Lit./h | 33.6 Lit./h | 47.7 Lit./h | ||||||
Temperature Reduction | 7°C | ||||||||
Efficiency Rating (3) | 2.7 COP | 9.23 EER | 2.9 COP | 9.90 EER | 3.2 COP | 10.93 EER |
Weights | Kg | Kg | Kg |
Net | 530 | 535 | 540 |
Operating (including LiCl) | 680 | 685 | 690 |
Dimensions | mm | Clearances | mm |
L | 2,240 | I | 1,000 |
W | 1,650 | ||
II | 500 | ||
H | 1,600 |
Notes:
TECHNICAL SPECIFICATIONS:
Unit Model | DH – 300 | DH – 500 | DH – 800 | |||
---|---|---|---|---|---|---|
Air Flow Capacities | ||||||
Supply (Treated) Air | M3/h 510 | CFM 300 | M3/h 850 | CFM 500 | M3/h 1,360 | CFM 800 |
Regeneration Air | M3/h 460 | CFM 270 | M3/h 765 | CFM 450 | M3/h 1,190 | CFM 700 |
Hot Water | 50°C to 90°C; Maximum flow 90 Lit./m | |||||
Cold Water / Glycol | (-) 10°C to 35°C; Maximum flow 90 Lit./m | |||||
Minimum ΔT between Cold & Hot water | 25°C | |||||
Desiccant Solution LiCl (Concentration 40%) |
55 Liters | |||||
Operation Temperature Range | (-) 10°C - 50°C | |||||
Operation Abs. Humidity Range | 1 g/Kg - 30 g/Kg | |||||
Electrical System | 230V, 1Ph, 50Hz |
208V, 1 Ph, 60Hz |
230V, 1Ph, 50Hz |
208V, 1 Ph, 60Hz |
230V, 1 Ph, 50Hz |
208V, 1 Ph, 60Hz |
Line Current Amp. | 3.6 | 4 | 3.6 | 4 | 5.6 | 6.1 |
Breaker Size Amp. | 16 | 16 | 16 | 16 | 16 | 16 |
Outdoor conditions at 30°C; 80 % R.H.
About Us:
In our world where time is of the essence, our team of highly skilled, experienced and well trained engineers are fully competent to carry out any kind of industrial dehumidification system issues and needs in a timely and professional manner. The annual turnover for the year 2010-2011, by Dry Air Systems & its Global Associate Companies was USD 10 Million.